Project Details

INDUSTRY SERVED:
ALUMINUM RECYCLING
APPLICATION: EXTRACTING THE HEAT FROM AN AREA OF MELT FURNACES. THIS COMPANY MELTS THE RECYCLED ALUMINUM WINDOW FRAMES AND MOLDS THEM INTO CYLINDERS FOR TRANSPORTING.
EQUIPMENT SUPPLIED:
6-AEROVENT EXHAUSTING ROOF VENTILATORS MODEL 48L422-BD40C-1089-15, 35,000 CFM EACH, 15 HP MOTORS, 210,000 CFM TOTAL
4-AEROVENT SIDE WALL SUPPLY FANS, MODEL 54L222-DDPRC-1145-15, 50,000 CFM EACH, 15 HP MOTORS, 200,000 CFM TOTAL SUPPLY AIR.
BENEFITS:
TEMPERATURES WOULD REACH 110F TO 120F IN THE MELT FURNACE AREAS ON HOT DAYS,
SO WE DESIGNED THE ROOF EXHAUST SYSTEM TO EXHAUST THE HOT AIR AND THEN PROVIDED FRESH AIR TO ENTER THE AREA WITH THE WALL FANS. WE TOOK OUT ABOUT 5% MORE AIR THAN WE BROUGHT INTO THE PLANT.
NOTES:
THE AEROVENT ROOF VENTILATORS DID A WONDERFUL JOB EXHAUSTING THE HOT AIR SO THE WORKFORCE COULD DO THEIR WORK IN A COOLER MORE COMFORTABLE ENVIRONMENT.
WE CAN OFFER DESIGN ASSISTANCE FOR THESE TYPES OF PROJECTS WITH A FULL LINE OF EXHAUST FANS AND SUPPLY FANS. THIS EQUIPMENT CAN HELP IN VENTILATING YOUR PLANT BY TAKING OUT THE HOT OR DIRTY AIR AND SUPPLY FRESH CLEAN OUTSIDE AIR. THIS TYPE SYSTEM WOULD PROVIDE YOUR WORKFORCE WITH A HEALTHIER, CLEANER ENVIRONMENT TO WORK. WHATEVER YOUR VENTILATION REQUIREMENTS MAY BE, WE CAN HELP IN PROVIDING EQUIPMENT TO MAKE YOUR ENVIRONMENT CLEANER AND HEALTHIER FOR YOUR WORK FORCE.
Additional Images
Does Your In-Plant Air Need To Be Cleaned and Cooled? CONTACT US